When more than three current conductors are bundled for more than 24", the ampacity must be adjusted
Jump to Connections
4,175 Views • Oct 3, 2024 • Click to toggle off description
When more than three current-carrying conductors are bundled (not maintain spacing) for more than 24 inches, the ampacity of the conductors at 90C [110.15(A)] must be adjusted in accordance with Table 310.15(C)(1). For example, the adjusted ampacity of 12 AWG , where there is nine current-carrying conductors bundled for more than 24 inches is 21A (30A x 70%).
Metadata And Engagement

Views : 4,175
Genre: Education
Uploaded At Oct 3, 2024 ^^


warning: returnyoutubedislikes may not be accurate, this is just an estiment ehe :3
Rating : 4.938 (6/379 LTDR)

98.44% of the users lieked the video!!
1.56% of the users dislieked the video!!
User score: 97.66- Overwhelmingly Positive

RYD date created : 2024-10-04T23:39:20.994225Z
See in json
Tags

oh hey i think you lost your tags look how to find one

Connections
Nyo connections found on the description ;_; report an issue lol

41 Comments

Top Comments of this video!! :3

@travishamilton1659

1 month ago

I love how its the same panel in most videos yet he gives use So many different code references using that same panel. Thank you mike. We appreciate everything

18 |

@court2379

1 month ago

I have chatted with people posting the super clean panels all bundled up about this. Arguing that if they are limited on the number of conductors through a knockout, they shouldn't bundle them in groups any more than that number either. The inner wires cannot cool properly.
Good to see the code actually addresses it.

4 |

@michaelgambetti2652

1 month ago

What’s the thought on bundling 10 NM cables horizontally in a stud space in a 2 inch hole. With a choke point every 16inches. Some inspectors might see that as bundling some do not?

|

@kylecanning9216

1 month ago

Does bundling apply to multiple mc's in bridal rings?

1 |

@willo9743

1 month ago

Was that a table vice holding the book

|

@BuzzElectricLlc

1 month ago

This means I can install (4) two wire circuits of 12 gauge thwn wire in a conduit without increasing the size of the conductors not including other factors correct?

1 |

@quillscollection5436

1 month ago

Apprentices think I'm a electrical god when I hit them in the head with this code. Lol

|

@ryanyork837

1 month ago

I don't zip tie anymore on solid wire. Keeping up with strict code changes makes you get lazy after so many years

1 |

@BuzzElectricLlc

1 month ago

Blk-wht...red-wht....blue-wht, org -wht and a green all 12 gauge thwn derated from 30 amps to 21 amps on a 20 amp breaker for a total of 4 circuits in a 3/4 conduit.....that's not the correct way to look at this?

1 |

@JeffPenaify

1 month ago

I vehemently oppose zip ties and “service loops” in a panel, form the wire square and if something gotta change in the future let the young bucks make a splice or two 😂 As some one who does panel swaps fairly regularly the constant zip ties and extra 3’ for each circuit is annoyin

1 |

@HappyNLost

1 month ago

My opinion wire nuts should never face down, Gravity's just looking to cause issues

|

@johnkulpowich5260

1 month ago

Codes were. made to be broken.
Unless you get caught