Neutral-to-ground bond at services and sub-panels explained.
Jump to Connections
7,568 Views • Nov 18, 2024 • Click to toggle off description
Service: A neutral conductor must be run to the service disconnecting means and it must be bonded to the metal service disconnect enclosure (main bonding jumper) in accordance with 250.24(C) and 250.142(A).
Feeder: A neutral-to-ground bond is not permitted at a 'sub-panel' at a building supplied by a feeder, see 250.24(B), 250.32(B), and 250.142(B).
#electrican #electricalcontractor #mikeholt #sparkylife #electricalapprentice
Metadata And Engagement

Views : 7,568
Genre: Education
Uploaded At Nov 18, 2024 ^^


warning: returnyoutubedislikes may not be accurate, this is just an estiment ehe :3
Rating : 4.94 (8/524 LTDR)

98.50% of the users lieked the video!!
1.50% of the users dislieked the video!!
User score: 97.75- Overwhelmingly Positive

RYD date created : 2024-11-23T15:05:35.375502Z
See in json
Tags

oh hey i think you lost your tags look how to find one

Connections
Nyo connections found on the description ;_; report an issue lol

19 Comments

Top Comments of this video!! :3

@9111logic

4 days ago

Thanks for reminding us, Bless you Mike 🙏

2 |

@MurffSurff

5 days ago

Yes sir, it’s an easy way for me to tell that the customer hired a non licensed person or uneducated in proper work to do electrical repairs in their house
At this point I know to watch out when doing anything electrical for them and to not believe the customer when they deny it
At this point I use my hourly rate which I double before I start any work
Sometimes I just have to leave because I find ground wire in Romex connected to plastic boxes with 120v on it and the customer doesn’t want me to address it first before installing a new device or troubleshooting
It’s really insane as well as such a fire hazard to have 120v possibly floating around on the grounding system just looking for a path
That is really “ objectionable voltage and current “
Thanks Mike

2 |

@radikaldesignz

5 days ago

This reminds me of something we needed to fix recently on a site where we needed to go around grounding everything in an older residential.

One of the light switch boxes had a neutral bonded to the box (metal). Also found a light switch box on the same breaker (which fed switched power to a nearby outlet) where the neutral wires were fried at the switch. Fixing that and removing the bonding on the other fixed everything.

Can you imagine?

"Can't find the short, dont want to check everything on 19 again... screw it, run the neutral through the box, all goes to the same place anyhow!" 😂😂

I'm surprised the house didn't burn down before we got to i

1 |

@paulbarton5159

5 days ago

Thanks Mike!

1 |

@bramcoteelectrical1088

5 days ago

Grounding, bonding, earthing and equipotential bonding and extraneous parts always gets most electricans pants in a twist 😂

Great information Mike 👍

2 |

@simplewick350

5 days ago

Unless its an older install with 2 ungrounded conductors and one grounded conductor no EGC. And meets the criteria of the exceptions provided in 250.32(B)(1)

1 |

@Es0ter1ca

5 days ago

HVAC guy here, love your stuff. I always picture it as, if you think it’s wrong to use a neutral as a ground anywhere else… why would you do it in a panel that ain’t the mains?

|

@cppoly

5 days ago

Mike can you do a similar video on grounding / bonding ahead of the service disconnect such how this is handled for a meter disconnect or emergency disconnect?

|